STRUCTURAL FIRE PROTECTION

Structural Engineering / Building Services | AT

Safety – Responsibility – Sustainability

For over 30 years, we have been manufacturing fire protection panels from materials that are harmless to health.

THERMAX® is always the first choice when it comes to using processor-friendly and sustainable fire protection solutions for building services and building construction.

Here you will find country-specific THERMAX® product descriptions, application examples, design descriptions with CAD drawings, safety data sheets and processing instructions for the Austrian market.

Brief overview of constructions with THERMAX® SL fire protection panels according to ETA-11/0083 SINTEF (06/2018) for:

Ventilation ducts EI60, EI90, EI120
Sheet metal duct cladding EI90
Smoke extraction ducts EI60, EI90, EI120
Installation ducts and shafts EI60, EI90, EI120

THERMAX® SL fire protection boards: ventilation duct, self-supporting

BezeichnungKlassifizierungMaterialdickeLeitungsabmessungBetriebsdruck
L2060EI 60 (ve ho o ↔ i) S1 x 35 mm≤ 1250 x 1000 mm (BxH) i.Li.± 500 Pa
L2090EI 90 (ve ho o ↔ i) S1 x 45 mm≤ 1250 x 1000 mm (BxH) i.Li.± 500 Pa
L2120EI 120 (ve ho o ↔ i) S 1 x 55 mm≤ 1250 x 1000 mm (BxH) i.Li.± 500 Pa

Single-shell, 4-sided ventilation duct with a
Fire resistance duration of 60, 90 or 120 minutes.
Larger duct dimensions are possible.

Tested according to EN 1366-1

THERMAX® SL fire protection boards: ventilation duct as cladding / sheathing

BezeichnungKlassifizierungMaterialdickeLeitungsabmessungBetriebsdruck
L1090EI 90 (ve ho o ↔ i) S1 x 45 mm≤ 1250 x 1000 mm (BxH)
Stahlblechleitung i.Li.
± 500 Pa

Single-skin, 4-sided ventilation duct as fire protection cladding for air ducts made of sheet steel, for a fire resistance duration of 90 minutes.

Tested according to EN 1366-1

THERMAX® SL Fire protection boards: Smoke extraction duct

BezeichnungKlassifizierungMaterialdickeLeitungsabmessungBetriebsdruck
L3060EI 60 (ve-ho) 500 multi1 x 35 mm≤ 1250 x 1000 mm (BxH) i.Li.± 500 Pa
L3090EI 90 (ve-ho) S 500 multi1 x 45 mm≤ 1250 x 1000 mm (BxH) i.Li.-1500/+500 Pa
L3120EI 120 (ve-ho) S 1500 multi1 x 55 mm≤ 1250 x 1000 mm (BxH) i.Li.-1500/+500 Pa

Single-shell, 4-sided smoke extraction duct with a fire resistance duration of 60, 90 or 120 minutes. Larger duct dimensions are possible.

Tested according to EN 1366-8

THERMAX® Fire protection boards: Installation ducts and shafts

BezeichnungKlassifizierungMaterialdickeLeitungsabmessung-
I1060EI 60 (ve ho o ↔ i)1 x 35 mm200 x 200 mm – 1250 x 1000 mm-
I1090EI 90 (ve ho o ↔ i)1 x 45 mm200 x 200 mm – 1250 x 1000 mm-
I1120EI 120 (ve ho o ↔ i)1 x 55 mm200 x 200 mm – 1250 x 1000 mm-

Single-shell, 4-sided installation ducts and shafts with a fire resistance duration of 60, 90 or 120 minutes. For all common installations, except cable trays.

Tested according to EN 1366-5